Jump to page content

Blaw Knox K1373 and K4611

Contents

Overview

Blaw Knox K1373 is an unusual suite of towers. The contract produced two separate sets of towers: double circuit 66 kV, and three-circuit towers that carry two 66 kV circuits and one 33 kV circuit below them. The appearance of the crossarms on the double circuit line towers earned the design the nickname “Christmas Tree”: each crossarm extends two feet further than the one above. The K1373 drawings primarily indicate that it covered Morley to Grassmoor. Spondon to Willoughby is briefly mentioned, and the dual voltage towers were used between Spondon and Morley but not listed as such on the drawings.

A related Blaw Knox K4611 contract covered Willoughby–Queniborough–Kibworth in Leicestershire. K4611 uses a different design of tower peak, although it’s uncertain to what extent this alternative peak design was included in K1373 (so far only found as a special version of the line tower).

K1373 was designed for 66 kV, but no lines presently operate at that voltage. Most lines have been uprated to 132 kV, perhaps possible due to what seems to be very generous clearances in the tower design (albeit smaller than those of regular 132 kV towers). The design of the K4611 DC-type tower for Willoughby–Queniborough was amended with outriggers for 132 kV operation but in reality this line is only strung for 33 kV; these outriggers can however be seen on other uprated 132 kV lines using the same towers. The remaining lines have been de-rated to 33 or 11 kV.

K4611 is also highly unusual in having a dedicated single-circuit transposition (SX) type; this is the only tower type that uses a standard designation. No other tower series is presently known to have an SX type.

General data

Designed for MIDESCO (Midland Electric Supply Company)
Design contract Blaw Knox K1373 and K4611
Found England
Height (straight line tower) 77′–0″ (23.5 m) (type A double-circuit line tower)
79′–4″ (24.2 m) (type DA double-circuit line tower)
76′–0″ (23.2 m) (type S three-circuit line tower)
68′–3″ (20.8 m) (type SA single-circuit line tower)
Voltage 66 kV, 66 + 33 kV (design)
132 kV (uprated lines)
Dates back to 1935–37 (drawings)
Known conductors Single
Circuit count Single-circuit 66 kV
Double-circuit 66 kV
Double-circuit 66 kV plus single-circuit 33 kV (three total)
Double-circuit 132 kV (uprated lines)
Normal span 700 feet

The wind span for the K1373 and K4611 suspension towers is 700 feet (and 1000 feet for the angle towers); the only tower type for which the span is presently known is K4611 SA, where 700 feet is also given.

Tower type designations

Neither K1373 nor K4611 use standard tower designations. Instead, a single letter denotes the tower body up to roughly the bend line and covers every purpose fulfilled by that tower body; K4611 added a prefix to this letter to indicate whether the tower was single (“S”) or double (“D”) circuit. The tower body above the bend line—including crossarm spacing—can vary without affecting the designation; in standard nomenclature the tower type designation describes the function of the tower without regard to which components may be shared with other tower types. The designations are as follows (standard double circuit designations in bold type):

Designation Circuits Roles
K1373 K4611
A DA Two:
2 × 66 kV
Line (D3, DD3)
B DB Angle (D20, DD20), transposition (DX)
C DC Angle (D60, DD60), terminal (DT, DDT)
S Three:
2 × 66 kV +
1 × 33 kV
Line (3°), 33 kV–only transposition
M Angle (20°), transposition
D Angle (60°), terminal
SA One:
1 × 66 kV
Line (S3)
SB Angle (S20)
SC Angle (S60)
SX Transposition

The tower angles are derived from the stress sheets for K1373 on the basis that the angles chosen for the working loads are the maximum angles intended for each tower type. The resulting angles tie in with other 33 kV and 66 kV tower types.

Lines

A single K4611 tower is used at Corby to terminate a 33 kV steel tower line.

Tower forms

Single circuit (K4611)

K4611 single circuit towers (no single circuit in K1373):

K4611 SA SEW
K4611 SA DEW
K4611 SB SEW
K4611 SB DEW
K4611 SC SEW
K4611 SC DEW
K4611 SX SEW
K4611 SX DEW
Willoughby terminal tower 1B

Willoughby terminal tower 1B no longer exists.

Double circuit (K1373 and K4611)

Standard double circuit towers. Designed for 66 kV but capable of operating at 132 kV.

The line from Willoughby to Ratcliffe-on-Soar uses a revised tower peak resembling that of PL16. This appears to correspond with the drawing depicting a revised peak that allows for 85° earthwire swing.

K1373 A SEW
K1373 A DEW
K1373 A special DEW
K1373 A (85° EW swing)
K4611 DA SEW
K4611 DA DEW
K1373 B SEW
K1373 B DEW
K4611 DB SEW
K4611 DB DEW
K1373 B transposition
K4611 DB transposition
K1373 C SEW
K1373 C DEW
K4611 DC SEW
K4611 DC DEW
K4611 DC higher-angle
K4611 DC transposition

The B-type transposition tower rigging is based on Google Street View depictions of “Baby PL16” 66 kV transposition towers; these use a crossarm arrangement virtually identical to K1373 and the rigging set-up corresponds sufficiently with the K4611 tower schematics.

A tower held to be the former terminal tower (now a through tower to a PL16 DT) at Annesley substation appears to be a DC with a custom top hamper. The same type is found in Newstead, Stanley Common and Loscoe for angles above 60°. The deviation angles are 67° for Loscoe and 72° for Newstead and Stanley Common. The higher-angle diagram above is a Street View-derived approximation, with weak assumptions made about the vertical dimensions owing to perspective distortion. The terminal tower at Annesley is possibly a DT45.

The existence of a combined transposition–angle tower was unexpected; this diagram is traced from a photograph from Zak Martin, of a tower found in Stanley Common.

Double-circuit terminal towers

K1373 double-circuit terminal towers
Grassmoor terminal tower
K1373 Spondon and Willoughby terminal towers

Neither terminal type is presently known to have survived. The standard A-type double earthwire type is also not known. Transposition towers remain on the Willoughby to Ratcliffe line.

The line from Morley to Grassmoor now terminates part-way along the route at Belper. A B-type (20°) tower has been converted to a terminal tower by the addition of bracing to the crossarms. The B-type body is not designed for termination but as this is a 33 kV line the conductors may be of a lower weight that can be handled on a B-type tower. This tower is depicted below, with its 20-foot height extension.

Belper terminal tower
K4611 double-circuit terminal towers

Willoughby substation:

Willoughby junction tower 1
Willoughby terminal tower 1A
Willoughby terminal tower 1C

Terminal tower 1A is one of the few towers found to have a lightning conductor fitted. K1373 and K4611 towers were all designed to take lightning conductors but they were only scheduled to be fitted to selected towers. Rannoch–Abernethy towers are another type that use lightning conductors.

Terminal tower 1C no longer exists.

South Croxton substation (Queniborough):

South Croxton terminal tower

132 kV uprated towers

The clearances on K1373 and K4611 towers are somehow great enough to allow the towers to be uprated to 132 kV operation. For larger angles, however, the C and DC towers require outriggers to maintain jumper clearances. K4611 drawing XM1631-50A from 1958 covers the addition of outriggers to the DC-type tower to support 132 kV uprating; a K1373 C tower at Willoughby is also adapted in this fashion.

K1373 C SEW, 132 kV
K1373 C DEW, 132 kV
K4611 DC SEW, 132 kV
K4611 DC DEW, 132 kV

Three circuit (K1373)

These towers carry three circuits, by design 66 kV double circuit above a single circuit of 33 kV. The 66 kV portion of the tower is symmetrical, with four phases across the middle crossarm tier, two per side. The 33 kV level is asymmetric, with two phases to one side and the third phase on the opposite side. The unusually wide spacing of the 33 kV phases is presumably to avoid conductor clashing rather than any need for such a wide air gap: the spans are longer than those of 33 kV wood pole lines.

No lines are known now that use the 33 kV crossarms for anything.

Full transposition uses M-type towers. There are also S-type towers used for transposing only the 33 kV circuit, suggesting that 33 kV was held to need transposing more frequently along the power line than 66 kV.

K1373 S SEW
K1373 S DEW
K1373 S 33 kV–only transposition SEW
K1373 S 33 kV–only transposition DEW
K1373 M SEW
K1373 M DEW
K1373 M transposition
K1373 D SEW
K1373 D DEW
K1373 D tower 1 (Spondon terminal)
K1373 D tower 31 (Morley terminal)

The Spondon terminal is a custom design with bizarre crossarms. The top crossarm is square-ended on top and pointed below. The top (earthwire and top phase) and middle crossarm levels have auxiliary crossarms but the bottom level does not. The bottom crossarm is pointed but the middle crossarm is square-ended and splayed on one side.

The following towers are of unclear purpose:

K1373 M (four-tier)
K1373 M (special crossarms)

Examples

Out of range.

Tower details

See dimensions on the site guide page for a key to the tables.

Tower dimensions
Type Source Height Base width Crossarm width
K1373 A SEW XM1180-107A 77′–3″ (23.5 m) 19′–0″ (5.8 m) 26′–6″ (8.1 m)
K1373 A DEW XM1180-113 76′–7″ (23.3 m) 19′–0″ (5.8 m) 26′–6″ (8.1 m)
K1373 A (85° EW swing) XM1180-119 76′–6″ (23.3 m) 19′–0″ (5.8 m) 26′–6″ (8.1 m)
K1373 B XM1180-106 72′–0″ (21.9 m) 22′–0″ (6.7 m) 27′–6″ (8.4 m)
K1373 B transposition XM1180-114A 72′–0″ (21.9 m) 22′–0″ (6.7 m) 33′–0″ (10.1 m)
K1373 C 60° XM1180-108A 72′–0″ (21.9 m) 23′–0″ (7.0 m) 28′–3″ (8.6 m)
K1373 C terminal XM1180-116, -123A 72′–0″ (21.9 m) 23′–0″ (7.0 m) 31′–0″ (9.4 m)
K1373 S SEW XM1180-10 76′–0″ (23.2 m) 19′–0″ (5.8 m) 42′–0″ (12.8 m)
K1373 S DEW XM1180-18A 75′–6″ (23.0 m) 19′–0″ (5.8 m) 42′–0″ (12.8 m)
K1373 S 33 kV-only transposition SEW XM1180-23A 76′–0″ (23.2 m) 19′–0″ (5.8 m) 42′–0″ (12.8 m)
K1373 S 33 kV-only transposition DEW XM1180-18A 75′–6″ (23.0 m) 19′–0″ (5.8 m) 42′–0″ (12.8 m)
K1373 M XM1180-17A, 18A 71′–0″ (21.6 m) 21′–0″ (6.4 m) 42′–0″ (12.8 m)
K1373 M transposition XM1180-24A 73′–0″ (22.3 m) 21′–0″ (6.4 m) 42′–0″ (12.8 m)
K1373 M (4-tier) XM1180-30A 80′–0″ (24.4 m) 21′–0″ (6.4 m) 28′–0″ (8.5 m)
K1373 M (special crossarms) XM1180-13 71′–0″ (21.6 m) 21′–0″ (6.4 m) 34′–0″ (10.4 m)
K1373 D XM1180-16A, 19A 71′–0″ (21.6 m) 23′–0″ (7.0 m) 52′–6″ (16.0 m)
K1373 D terminal (Spondon) XM1180-31B, 71′–0″ (21.6 m) 23′–0″ (7.0 m) 44′–0″ (13.4 m)
K1373 D terminal (Morley) XM1180-27 71′–0″ (21.6 m) 23′–0″ (7.0 m) 44′–0″ (13.4 m)
K4611 DA XM1631-4A 79′–4″ (24.2 m) 19′–0″ (5.8 m) 26′–6″ (8.1 m)
K4611 DB XM1631-8A, K4611-29A 74′–9″ (22.8 m) 22′–0″ (6.7 m) 27′–6″ (8.4 m)
K4611 DB transposition XM1631-17A 74′–9″ (22.8 m) 22′–0″ (6.7 m) 33′–0″ (10.1 m)
K4611 DC K4611-28C 75′–0″ (22.9 m) 23′–0″ (7.0 m) 28′–3″ (8.6 m)
K4611 SA XM1631-5A 68′–3″ (20.8 m) 12′–6″ (3.8 m) 21′–6″ (6.6 m)
K4611 SB XM1631-18A 64′–6″ (19.7 m) 15′–0″ (4.6 m) 21′–6″ (6.6 m)
K4611 SC XM1631-20 64′–6″ (19.7 m) 17′–6″ (5.3 m) 24′–0″ (7.3 m)
K4611 SX XM1631-16 67′–6″ (20.6 m) 15′–0″ (4.6 m) 24′–0″ (7.3 m)
Willoughby tower 1A XM1631-32A 65′–3″ (19.9 m) 17′–6″ (5.3 m) 24′–6″ (7.5 m)
Vertical spacing, K1373
Tower type Peak to top crossarm Top to middle crossarm Middle to bottom crossarm Bottom crossarm to ground
A 5′–6″ ¹ 11′–0″ 10′–9″ 50′–0″
B, C 7′–0″ 10′–6″ 10′–6″ 44′–0″
S ² 4′–6″ 11′–9″ 12′–9″ 47′–0″
M 20° 6′–0″ 10′–6″ 10′–6″ 44′–0″
D 60°
D (Morley terminal)
S transposition 4′–6″ 11′–9″ 15′–9″ 47′–0″
M transposition 6′–0″ 11′–6″ 13′–6″ 44′–0″
D (Spondon terminal) 6′–0″ 10′–6″ 12′–0 44′–0″

For some towers the dimensions vary between drawings:

  1. Depending on the drawing, K1373 A top crossarm to peak is given as 4′–0″ foot (wire clearance diagram and GA 85° earthwire swing), 4′–6″ (stress diagram), 5′–3″ (GA) and 5′–6″ (ED); for double earthwire, it’s 4′–10″. It’s meant to be 4′ to the earthwire position, but some drawings take this to be the height to the underside of the peak cap.
  2. There is conflicting data for all the vertical clearances of K1373 S.
Vertical spacing, K4611 double circuit
Tower type Peak to earthwire crossarm EW crossarm to top crossarm Top to middle crossarm Middle to bottom crossarm Bottom crossarm to ground
DA DEW 2′–9″ 4′–10″ 11′–0″ 10′–9″ 50′–0″
DA SEW 7′–7″
DB DEW 2′–9″ 7′–0″ 10′–6″ 10′–6″ 44′–0″
DB SEW 9′–9″
DC DEW 2′–9″ 7′–3″
DC SEW 10′–0″
Vertical spacing, K4611 single circuit
Tower type Peak to earthwire crossarm EW crossarm to top crossarm Top to bottom crossarm Bottom crossarm to ground
SA DEW 2′–9″ 4′–9″ 11′–0″ 50′–0″
SA SEW 7′–3″
SB DEW 2′–6″ 7′–0″ 44′–0″
SB SEW 9′–6″
SC DEW 2′–6″ 7′–0″
SC SEW 9′–6″

Examples

Out of range.

See also