Overview

T163 is a distribution tower type designed by Milliken Brothers. T163 was used for contract NWE SL2. Based on the schematics, the D10° tower is of the suspension type just as with Milliken E177 and Milliken PL1, although it has so far only been seen without deviation or with tension insulators (tension insulators also being found on some D3 towers). “N.W.E. S.L. 2.” is only an annotation and may not be the original contract for which the towers were designed; the recovered drawings note only “Contract T163” with no details of the contracting organisation or power line contract.

The general arrangement drawing for the D10 tower (LT629-23) has been annotated “.075 conductor”; the conductor type (HDBC, SCA, SCC etc) is not noted.

General data

Design contract Milliken Brothers T163
Height (straight line tower) 60′–9″ (18.5 m)
Voltage
Dates back to 1929–1930 (drawings)
Known conductors Single
Design conductor ?
Circuit count Double
Drawing ranges T163 / LT629

Lines

Lines suspected to use this tower type include:

Tower forms

The following diagrams are shown to scale at 12 pixels per metre:

Milliken T163 D3
Milliken T163 D10

The D10 towers both in Wiltshire and in Carlisle have a bottom panel of the basic tower that does not match the official drawing. The drawing appears to be correct, unless the towers have been modified in later life.

Examples

Out of range.

Tower details

See dimensions on the site guide page for a key to the tables. Base width for the D3 is back-to-back across top of stubs.

Type Source Height Base width Overall width
D3 15_13074_100 60′–9″ (18.5 m) 8′–5″ (2.6 m) 17′–5″ (5.3 m)
D10 LT629-23 63′–0″ (19.2 m) 13′–0″ (4.0 m) 20′–4″ (6.2 m)
Vertical spacing
Tower type Peak to top crossarm Top to middle crossarm Middle to bottom crossarm Bottom crossarm to ground
D3 2′–6″ 7′–0″ 7′–0″ 44′–3″
D10 2′–6″ 8′–3″ 7′–0″ 45′–3″